Modbus – IAI America ROBO Cylinder Series User Manual

Page 126

Advertising
background image

5. Modbus RTU

118

Modbus

5.4.3 Servo ON/OFF <<SON>>

(1) Function

Control ON/OFF of the servo.

When “Servo ON” is specified by the new data, the servo will turn ON after elapse of the

manufacturer parameter “Servo ON delay time.” However, the following conditions must be

satisfied:

x

The EMG status bit in device status register 1 is 0.

x

The major failure status bit in device status register 1 is 0.

x

The enable status bit in device status register 2 is 1.

x

The auto servo OFF status in the system status register is 0.

(2) Query Format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

0403

Servo ON/OFF command

Changed data [H]

2

Arbitrary

Servo ON: FF00

H

Servo OFF: 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

* If a teaching pendant or PC software is connected before the control establishes communication

with the host, the servo is turned OFF, and then the teaching pendant/PC software is removed,

the servo cannot be turned ON/OFF via commands received from with the host.

In this case, restore the RC controller power, or make sure the SIO port connection is removed

while the servo is ON.

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response

will be returned.