6. Modbus

ASCII

250

Modbus

6.5.7 Home return <<HOME>>

(1) Function

Home return operation will start if a rising edge in the home return command signal is detected (the

data is first set to 0000

H

and then changed to FF00

H

). Once the home return is completed, the

HEND bit will become 1. This command can be input as many times as desired even after home

return has been completed once.

(2) Query format

Field

Number of

characters

ASCII mode

character string

(fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is specified

Function code [H]

2

‘0’, ‘5’

Write to a single coil DO.

Start address [H]

4

‘0’, ‘4’ ‘0’, ‘B’

Home return command

Changed data [H]

4

Arbitrary

Execute home return: ‘F’, ‘F’, ‘0’, ‘0’

Normal: ‘0’, ‘0’, ‘0’, ‘0’

Error check [H]

2

LRC calculation

result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

Note If a teaching pendant or PC software is connected, the servo is turned OFF, and then the

teaching pendant/PC software is removed, all before the control establishes communication

with the host, the servo cannot be turned ON/OFF via commands received from with the host.

In this case, restore the controller power, or make sure the connected tool of the SIO port is

removed while the servo is ON.

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response will

be returned.