6. Modbus

ASCII

217

Modbus

6.4.13 Controller Status Signal Reading 3 <<DSSE>>

(1) Function

Internal statuses (expansion device) of the controller are indicated.

[Refer to 4.3.2 (14), “Data of expansion device status registers.”]

(2) Query format

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Start address [H]

4

‘9’, ‘0’, ‘0’, ‘7’

Expansion device status

register

Number of registers [H]

4

‘0’, ‘0’, ‘0’, ‘1’

Reading address 9007

H

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Number of data bytes [H]

2

‘0’, ‘2’

Reading 1 register

= 2 bytes.

Data [H]

4

Expansion status

Expansion status [Hex]

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

15