Modbus – IAI America ROBO Cylinder Series User Manual

Page 151

Advertising
background image

5. Modbus RTU

143

Modbus

*1 If the CLBR is turned OFF during this period, calibration will not be performed because the signal is

not yet recognized as having been input.

*2 If the CLBR is turned OFF during this period, an alarm will generate.

(4) Response

A response message to be sent following a successful change should be the same as the query.

If any invalid data has been sent, an exception response (refer to 7) will be returned or no

response will be returned at all.

(5) Example of use

Calibrate the dedicated load cell connected to controller axis 0.

Query (Silent intervals are inserted before and after the query.)

01 05 04 26 FF 00 6C C1

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

05

Start address [H]

0426

Changed data [H]

FF00

Error check [H]

6CC1 (in accordance with

CRC calculation)

End

Silent interval

If the change is successful, the response message will be the same as the query.

Input is recognized after

the signal remains ON for

20 ms

*1

.

Calibration time

*2

CLBR

CEND

Turn OFF the CLBR after confirming

that the CEND has turned ON.

When the calibration was successful, the CEND turns ON.

While the CLBR is OFF, the CEND remains OFF.