5. Modbus RTU

77

Modbus

5.3.7 Current Position Reading <<PNOW>> (in 0.01 mm units)

(1) Function

This bit reads the current position in units of 0.01 mm. The sign is effective.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9000

Current position monitor

Number of registers [H]

2

0002

Reading addresses 9000

H

to

9001

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

04

Reading 2 registers = 4 bytes

Data 1 [H]

2

In accordance with

the current position

data

Current position data [Hex]

(most significant digit)

Data 2 [H]

2

In accordance with

the current position

data

Current position data [Hex]

(least significant digit)

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

9