5. Modbus RTU

79

Modbus

5.3.8 Present Alarm Code Reading <<ALMC>>

(1) Function

This query reads the code indicating the normal status or alarm status of the controller.

In the normal status, 00

H

is stored.

[For details on alarm codes, refer to the operation manual for each controller.]

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bits data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9002

Present alarm code

Number of registers [H]

2

0001

Reading address 9002

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bits data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

02

Reading 1 register = 2 bytes

Data 1 [H]

2

Alarm code

Alarm code [Hex]

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

7