Modbus – IAI America ROBO Cylinder Series User Manual

Page 311

Advertising
background image

7. T
roubleshooting

303

Modbus

Example of exception response generation

(Sample query message using Read Input Status)

Field

Sample value

[Hex]

ASCII mode

character string

RTU mode

8 bits [Hex]

Header

‘:’

None

Slave address

03

H

‘0, ’ ‘3’

03

H

Function code

02

H

‘0, ’ ‘2’

02

H

Start address [H]

04

H

‘0, ’ ‘4’

04

H

Start address (L)

A1

H

‘A, ’ ‘1’

A1

H

Number of DIs [H]

00

H

‘0, ’ ‘0’

00

H

Number of DIs (L)

14

H

‘1, ’ ‘4’

14

H

Error check

LRC (2 characters)

CRC (16 bits)

Trailer

CR/LF

None

Total bytes

17

8

If input status 04A1H does not exist, the following exception response will be returned.

Sample exception response from a slave

Field

Sample value

[Hex]

ASCII mode

character string

RTU mode

8 bits [Hex]

Header

‘:’

None

Slave address

03

H

‘0, ’ ‘3’

03

H

Function code

82

H

‘8, ’ ‘2’

82

H

Exception code

02

H

‘0, ’ ‘2’

02

H

Error check

LRC (2 characters)

CRC (16 bits)

Trailer

CR/LF

None

Total bytes

11

5

The exception response consists of the slave address field, function code field, and data field. In the slave

address field, the applicable slave address is set as in the slave address field of a “successful” response.

In the function code field, the function code in the query is set, and then the MSB (most significant bit of

the function code) of this field is set to 1. This allows the master to recognize that the message is not a

“successful” response, but an exception response. An exception code indicating the content of exception

is set in the data field.