5. Modbus RTU

146

Modbus

5.4.17 Deceleration Stop <<STOP>>

(1) Function

The actuator will start decelerating to a stop when the deceleration stop command edge (write

FF00

H

) is turned on.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

042C

Deceleration stop setting

Changed data [H]

2

Arbitrary

Deceleration stop command

(ON): FF00

H

* The controller automatically

resets the value to 0000

H

.

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response

will be returned.