Modbus – IAI America ROBO Cylinder Series User Manual

Page 281

Advertising
background image

6. Modbus

ASCII

273

Modbus

(3) Query format

Specify the address and data of the register whose data is to be changed in the query message.

Data to be changed shall be specified as 16-bit data in the changed data area of the query.

Field

Number of characters

(Number of bytes)

ASCII mode

fixed character

string

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

2

‘0’, ‘6’

Writing to registers

Start address [H]

4

Arbitrary

Refer to 6.6.1 (2), “Start

address list.”

Changed data [H]

4

4.3.2 (5) to 4.3.2. (7),

Refer to “List of changed

data.”

Error check [H]

2

LRC calculation

result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(4) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response will

be returned.