5. Modbus RTU

134

Modbus

5.4.11 Position Data Load Command <<TEAC>>

(1) Function

The current position is acquired by writing this command (write FF00H) when the teaching mode

command (5.4.10) is FF00H (teaching command).

The current position data will be written in the position number specified by the position number

specification register when the aforementioned condition was detected.

If other position data fields are empty, the default parameter values will be written at the same

time in the empty fields other than the target position (positioning band INP, speed VCMD,

acceleration/deceleration speed ACMD, and control flag CTLF).

After sending this command (write FF00

H

), keep the status as is for 20 ms or longer.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

0415

Position data load command

Changed data [H]

2

Arbitrary

Position data load command: FF00

H

Normal: 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response

will be returned.