5. Modbus RTU

91

Modbus

5.3.12 Controller Status Signal Reading 2 <<DSS2>>

(1) Function

This bit reads the internal status of the controller.

[Refer to 4.3.2 (13), “Data of device status register 2.”]

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9006

Device status register 2

Number of registers [H]

2

0001

Reading address 9006

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Internal status of controller

Number of data bytes [H]

1

02

Reading 1 register = 2 bytes

Data [H]

2

Status 2

Status 2 [Hex]

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

7