Modbus – IAI America ROBO Cylinder Series User Manual

Page 202

Advertising
background image

6. Modbus

ASCII

194

Modbus

6.4.4 Total moving distance Reading <<ODOM>> (in 0.01 mm units)

(1) Function

This bit reads the total moving distance in units of 1m.

(2) Query format

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Register reading

Start address [H]

4

‘8’, ‘4’, ‘0’, ‘2’

Total moving distance

Number of registers [H]

4

‘0’, ‘0’, ‘0’, ‘2’

Reading addresses 8402

H

to 8403

H

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Register reading

Number of data bytes [H]

2

‘0’, ‘4’

Reading 2 registers

= 4 bytes

Data 1 [H]

4

Total moving distance

Total moving distance

[Hex] (most significant

digit)

Data 2 [H]

4

Total moving distance

Total moving distance

[Hex] (least significant

digit)

Error check [H]

2

LRC calculation result

Trailer

2

CR’, ‘LF’

Silent interval

Total number of bytes

19