6. Modbus

ASCII

240

Modbus

6.5.2 Safety Speed Enable/Disable Switching (SFTY)

(1) Function

This query enables/disables the speed specified by user parameter No. 35, “Safety speed.”

Enabling the safety speed in the MANU mode will limit the speeds of all movement commands.

(2) Query format

Field

Number of

characters

ASCII mode

character string

(fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is specified

Function code [H]

2

‘0’, ‘5’

Write to a single coil DO.

Start address [H]

4

‘0’, ‘4’ ‘0’, ‘1’

Safety speed command

Changed data [H]

4

Arbitrary

Safety speed enabled: ‘F’, ‘F’, ‘0’, ‘0’

Safety speed disabled: ‘0’, ‘0’, ‘0’, ‘0’

Error check [H]

2

LRC calculation

result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response will

be returned.