Modbus – IAI America ROBO Cylinder Series User Manual

Page 77

Advertising
background image

5. Modbus RTU

69

Modbus

(4) Query sample

A sample query that reads the total moving count (addresses 8400

H

to 8401

H

) of a controller with

axis No. 0 is shown below.

z

Query (silent intervals are inserted before and after the query)

01 03 84 00 00 02 EC FB

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Start address [H]

8400

Number of registers [H] 0002

Error check [H]

ECFB (in accordance with

CRC calculation)

End

Silent interval

The response to the query is as follows.

z

Response (silent intervals are inserted before and after the response)

01 03 04 00 00 02 1F BA 9B

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Number of data bytes [H] 04 (4 bytes = 2 registers)

Data 1 [H]

00 00

Data 2 [H]

02 1F

Error check [H]

BA9B (in accordance with CRC calculation)

End

Silent interval

The Total moving count is “21F

H

” o Convert into decimal number o 543[times]

Note The data of the response example is simply an example and will vary depending on

various conditions.