6. Modbus

ASCII

235

Modbus

6.4.22 Controller Status Signal 5 <<SSSE>>

(1) Function

This query reads the internal operation status of the controller.

[Refer to 4.3.2 (19), “Data of expansion system status register.”]

(2) Query format

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Start address [H]

4

‘9’, ‘0’, ‘1’, ‘5’

Expansion system status

register

Number of registers [H]

1

‘0’, ‘0’, ‘0’, ‘1’

Reading address 9015

H

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

14

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of characters

ASCII mode

character string

(fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Internal status of controller

Number of data bytes [H]

2

‘0’, ‘2’

Reading 1 registers = 2 bytes

Data [H]

4

Expansion system

status

Expansion system status

[Hex]

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

15