Modbus – IAI America ROBO Cylinder Series User Manual

Page 289

Advertising
background image

6. Modbus

ASCII

281

Modbus

Bit 4 (GSL0), 5 (GSL1) = Refer to the table below. (These bits can be set only on SCON-CA/CFA

controllers.)

GSL1

GSL0

Function

0

0

Select parameter set 0 (default).

0

1

Select parameter set 1

1

0

Select parameter set 2

1

1

Select parameter set 3

You can register a maximum of four servo gain parameter sets consisting of six

parameters and move the actuator to each position by selecting a different

parameter set every time. [For details, refer to the operation manual for your

controller.]

Bit 6 (MOD0), 7 (MOD1) = Refer to the table below.

These bits cannot be set on PCON-* and

ERC2/ERC3 controllers.)

MOD1

MOD0

Function

0

0

Trapezoid pattern (default)

0

1

S-motion

1

0

Primary delay filter

1

1

Cannot be used.

These signals are used to select the acceleration/deceleration pattern

characteristics. Set one of the patterns before issuing an actuator movement

command. [For details, refer to the operation manual for your controller.]

Bit 12 (NTC0), 13 (NTC1) = Refer to the table below. (These bits can be set only on SCON-CA

controllers.)

NTC1

NTC0

Function

0

0

Do not use vibration control

(default).

0

1

Select parameter set 1

1

0

Select parameter set 2

1

1

Select parameter set 3

When vibration control is used, you can register a maximum of three parameter

sets and move the actuator to each position by selecting a different parameter

set every time. [For details, refer to the operation manual for your controller.]

Advertising