Did the problem occur after moving facilities?

Occurred after moving facilities o (1) Disconnection of communication cables o Fix disconnection

(2) Loosening of connectors for communication cables

o

Check connection

(3) Wrong control communication speed setting

o

Refer to "3.2. (1) Precautions o Check *6

Did the problem occur after adding controllers?

Occurred after adding controllers o (1) Wrong axis number settings for additional controllers o Check *4

(2) Wrong communication speed setting for additional controllers

o

Check *6

(3) Wrong transmitter activation time setting for additional controllers

o

Check parameter No. 17

(4) Wrong terminating resistor mounting position

o

Mount the terminating resistor on the junction furthest

from the master (host). (Refer to Section 3.)

Was a new device started up (including newly introduced devices with existing settings)?

Cannot communicate with any controllers?

Check connection using the PC software for RC. *1

Cannot communicate with any controllers o (1) Wrong wiring of communication cables between

the host and junction o Check wiring *3

(2) Device power supply error

o

Check power supply voltage o Check that

the 0 V line is used commonly for all devices

o

Use the 0 V line commonly for all devices.

(3) Overlapping setting of controller axis numbers

o

Check *4

(4) Inconsistent controller communication speed

setting o Check *6

Cannot communicate with specific controllers.o (1) Wrong wiring of communication cables

between controllers and junction

o

Check wiring *3

(2) Device power supply error

o

Check power supply voltage

(3) Overlapping setting of controller axis numbers

o

Check *4

(4) Inconsistent controller communication speed

setting o Check *6

Can communicate. o [1] Inadequate host

programs

(1) Check programs again *5

(2) Check communication speed setting again *2