6. Modbus

ASCII

213

Modbus

6.4.11 Controller Status Signal Reading <<DSS1>>

(1) Function

This query reads the internal status of the controller.

[Refer to 4.3.2 (12), “Data of device status register 1”.]

(2) Query format

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Start address [H]

4

‘9’, ‘0’, ‘0’, ‘5’

Device status register 1

Number of registers [H]

4

‘0’, ‘0’, ‘0’, ‘1’

Reading address 9005

H

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(3) Response format

A response message contains 16 bits of data per address.

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Number of data bytes [H]

2

‘0’, ‘2’

Reading 1 register

= 2 bytes

Data [H]

4

Status 1

Status 1 [Hex]

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

15