Modbus – IAI America ROBO Cylinder Series User Manual

Page 224

Advertising
background image

6. Modbus

ASCII

216

Modbus

(4) Sample query

A sample query that reads the device status 2 (address 9006

H

) in a controller of axis No. 0 is shown

below.

Query: 01 03 90 06 00 01 65 [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Start address [H]

‘9’, ‘0’, ‘0’, ‘6’

39303036

Number of registers [H]

‘0’, ‘0’, ‘0’, ‘1’

30303031

Error check [H]

‘6’, ‘5’ (In accordance with LRC calculation) 3635

End

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 01 03 02 80 00 7A [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H]

‘0’, ‘2’ (2 bytes = 1 register)

3032

Data 1 [H]

‘8’, ‘0’, ‘0’, ‘0’

38303030

Error check [H]

‘7’, ‘A’ (In accordance with LRC calculation) 3741

End

‘CR’, ‘LF’

0D0A

Note The data of the response example is simply an example and will vary depending on

various conditions.