5. Modbus RTU

89

Modbus

5.3.11 Controller Status Signal Reading 1 <<DSS1>>

(1) Function

This bit reads the internal status of the controller.

[Refer to 4.3.2 (12), “Data of device status register 1.”]

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9005

Device status register 1

Number of registers [H]

2

0001

Reading address 9005

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per address.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

02

Reading 1 register = 2 bytes

Data [H]

2

Status 1

Status 1 [Hex]

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

7