6. Modbus

ASCII

236

Modbus

(4) Query sample

A sample query that reads the expansion system status register (address 9015

H

) of a controller of

axis No. 0 is shown below.

Query: 01039015000156 [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Start address [H]

‘9’, ‘0’, ‘1’, ‘5’

39303135

Number of registers [H]

‘0’, ‘0’, ‘0’, ‘1’

30303031

Error check [H]

‘5’, ‘6’ (in accordance with LRC

calculation)

3536

End

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 0103020100F9 [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H]

‘0’, ‘2’ (2 bytes = 1 register)

3032

Data 1 [H]

‘0’, ‘1’, ‘0’, ‘0’

30313030

Error check [H]

‘F’, ‘9’ (in accordance with LRC

calculation)

4639

End

‘CR’, ‘LF’

0D0A

Note The data of the response example is simply an example and will vary depending on

various conditions