6. Modbus

ASCII

244

Modbus

6.5.4 Alarm Reset <<ALRS>>

(1) Function

When the alarm reset edge is turned on (the data is first set to FF00

H

and then changed to 0000

H

),

alarms will be reset.

If any alarm cause has not been removed, the same alarm will be generated again. If the alarm

reset edge is turned on while the actuator is paused,

the remaining travel will be cancelled.

When alarms are reset, make sure to write changed data of 0000

H

to restore the normal status.

(2) Query format

Field

Number of

characters

ASCII mode

character string

(fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is specified

Function code [H]

2

‘0’, ‘5’

Write to a single coil DO.

Start address [H]

4

‘0’, ‘4’ ‘0’, ‘7’

Alarm reset command

Changed data [H]

4

Arbitrary

Execute alarm reset: ‘F’, ‘F’, ‘0’, ‘0’

Normal: ‘0’, ‘0’, ‘0’, ‘0’

Error check [H]

2

LRC calculation

result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response will

be returned.