Modbus – IAI America ROBO Cylinder Series User Manual

Page 134

Advertising
background image

5. Modbus RTU

126

Modbus

5.4.7 Home Return <<HOME>>

(1) Function

Home return operation will start if a rising edge in the home return command signal is detected

(the data is first set to 0000

H

and then changed to FF00

H

). Upon home return completion, the

HEND bit will become 1. This command can be input as many times as desired even after home

return completion.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

040B

Home return command

Changed data [H]

2

Arbitrary

Execute home return: FF00

H

Normal: 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

* The servo must be ON before a home return command is issued.

If a teaching pendant or PC software is connected before the control establishes communication

with the host, the servo is turned OFF, and then the teaching pendant/PC software is removed,

the servo cannot be turned ON/OFF via commands received from with the host.

In this case, restore the RC controller power, or make sure the SIO port connection is removed

while the servo is ON.

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response

will be returned.