Modbus – IAI America ROBO Cylinder Series User Manual

Page 152

Advertising
background image

5. Modbus RTU

144

Modbus

5.4.16 PIO/Modbus Switching Setting <<PMSL>>

(1) Function

PIO external command signals can be enabled or disabled.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

0427

PIO/Modbus switching setting

Changed data [H]

2

Arbitrary

*1 Enable Modus commands: FF00

H

Disable Modbus commands: 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

*1 x Enable Modbus commands (ON) (disable PIO command): FF00

H

Operation via PIO signals is not possible.

x

Disable Modbus commands (OFF) (enable PIO command): 0000

H

Operation via external PIO signals is possible.

Supplement If the Modbus command is enabled, the PIO status at change is maintained.

If the Modbus command is switched to disabled, the operation status changes

according to the current PIO status. Note that even if the status of signals that

operate via edge detection has been changed, edge detection is ignored.

(3) Precaution

„

On a model equipped with an operation mode switch, “Enable PIO commands” will be specified

when the switch is set to the AUTO mode, or “Disable PIO commands” will be specified when

the switch is set to the MANU mode.

„

On a non-PIO model, the default setting is “Disable PIO commands.”

„

If IAI’s tool (teaching pendant or PC software) is connected, “Teaching modes 1, 2” and

“Monitor modes 1, 2” are available as tool modes. The correspondence between these modes

and PIO enable/disable specifications are as follows:

“Monitor modes 1, 2” o “Enable PIO commands”

“Teaching modes 1, 2” o “Disable PIO commands”