Modbus – IAI America ROBO Cylinder Series User Manual

Page 212

Advertising
background image

6. Modbus

ASCII

204

Modbus

(4) Sample query (Axis No. 0)

A sample query that reads address 9002

H

in an RC controller of axis No. 0 is shown below:

Query: 01039002000169 [CR][LF]

Field

ASCII mode

fixed character string

Converted ASCII code

data [H]

Header

‘:’

3A

Slave address

‘0’, ‘1’

3031

Function code

‘0’, ‘3’

3033

Start address

‘9’, ‘0’, ‘0’, ‘2’

39303032

Number of registers

‘0’, ‘0’, ‘0’, ‘1’

30303031

Error check

‘6’, ‘9’

3639

Trailer

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 01030200E812 [CR][LF]

Field

ASCII mode

fixed character string

Converted ASCII code

data [H]

Header

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H] ‘0’, ‘2’ (2 bytes = 1 register)

3032

Data 1 [H]

‘0’, ‘0’, ‘E’, ‘8’

30304538

Error check [H]

‘1’, ‘2’ (in accordance with

LRC calculation)

3132

Trailer

‘CR’, ‘LF’

0D0A

The most important alarm presently detected is “0E8”

H

, which is a phase A/B open alarm.

[For details on alarm codes, refer to the operation manual that comes with each controller.]

Note The data of the response example is simply an example and will vary depending on various

conditions.