5. Modbus RTU

103

Modbus

5.3.18 Total Time after Power On Reading <<STIM>>

(1) Function

This bit reads the total time since the controller power was turned on. The unit is ms.

The timer value is not cleared by software reset.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9010

System timer

Number of registers [H]

2

0002

Reading addresses 9010

H

to

9011

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

04

Reading 2 registers = 4 bytes

Data [H]

4

System timer

System timer [Hex]

The unit is ms.

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

9