Modbus – IAI America ROBO Cylinder Series User Manual

Page 157

Advertising
background image

5. Modbus RTU

149

Modbus

(3) Query format

Specify the address and data of the register whose data is to be changed in the query message.

Data to be changed shall be specified as 16-bit data in the changed data area of the query.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

06

Writing to registers

Start address [H]

2

Arbitrary

Refer to 5.5.1 (2), “Start

address list.”

Changed data [H]

2

Arbitrary

4.3.2 (5) to 4.3.2. (7)

Refer to List of changed data.

Error check [H]

2

In accordance with

the calculation result

End

None

Silent interval

Total number of bytes

8

(4) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response

will be returned.