5. Modbus RTU

174

Modbus

(6) Sample query

A sample query that rewrites all data of position No. 12 of axis No. 0 is shown below.

Axis No. 0

Target

position

(mm)

Positioning

band

(mm)

Speed

(mm/sec)

Individual

zone

boundary+

(mm)

Individual

zone

boundary-

(mm)

Acceleration

(G)

Deceleration

(G)

Push

(%)

Threshold Movement

control

100

0.1

200

60

40

0.01

0.3

0

0

Normal

movement

„

Query (silent intervals are inserted before and after the query)

01 10 10 C0 00 0F 1E 00 00 27 10 00 00 00 0A 00 00 4E 20 00 00 17 70 00 00 0F A0 00 01

00 1E 00 00 00 00 00 00 70 1E

„

Received response 01 10 10 C0 00 0F 84 F1

--- The query message is copied, except for the number of bytes and new data, and returned

as a response.

„ᴾ

Breakdown of Query Message

Field

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address

01

H

Axis No. 0 + 1

Function code

10

H

Start address

10C0

H

The start address is the target position specification

register 10C0

H

for position No. 12. *1

Number of registers

000F

H

Total 15 registers of register symbols PCMD to

CTLF are specified to be written.

Number of bytes

1E

H

15 (registers) x 2 = 30 (bytes) o 1E

H

0000

H

All upper bits of the 32-bit data are 0.

New data 1, 2

(target position)

Input unit (0.01 mm)

2710

H

100 (mm) x 100 = 10000 o 2710

H

0000

H

All upper bits of the 32-bit data are 0.

New data 3, 4

(positioning band)

Input unit (0.01 mm)

000A

H

0.1 (mm) x 100 = 10 o 000A

H

0000

H

All upper bits of the 32-bit data are 0.

4E20

H

200 (mm/sec) x 100 = 20000 o 4E20

H

New data 5, 6 (speed)

Input unit (0.01 mm/sec)

0FA0

H

40 (mm) x 100 = 4000 o 0FA0

H

Continue to the next page