Modbus – IAI America ROBO Cylinder Series User Manual

Page 136

Advertising
background image

5. Modbus RTU

128

Modbus

5.4.8 Positioning Start Command <<CSTR>>

(1) Function

If the rising edge of the positioning start command is detected (the data is first set to 0000

H

and

then changed to FF00

H

), the actuator will move to the position specified by the position number

stored in the position number specification register (POSR:0D03

H

). If nothing is done after the

position start command (FF00

H

is read and no new data is written), a position complete will not be

output even when the actuator enters the positioning band (write 0000

H

and restore the normal

status).

If this command is executed when home return has never been performed after the power was

turned on (when the HEND bit is 0), the actuator will perform home return and then start moving to

the target position.

* The target position, speed and all other operation parameters must be set in the position table

(nonvolatile memory) of the controller in advance.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

040C

Positioning start command

Changed data [H]

2

Arbitrary

Positioning start command:

FF00

H

Normal: 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response

If the change is successful, the response message will be the same as the query.

If invalid data is sent, an exception response (refer to section 7) will be returned, or no response

will be returned.

Advertising