Modbus, Communication 43, Dss1) – IAI America ROBO Cylinder Series User Manual

Page 51

Advertising
background image

4. Communication

43

Modbus

(12) Data of device status register 1 (Address = 9005

H

) (DSS1)

Bit

Symbol

Name

Function

15

EMGS

EMG status

0: Emergency stop not actuated

1: Emergency stop actuated

This bit indicates whether or not the controller is currently in the emergency stop mode due to

an emergency stop input, cutoff of the drive source, etc.

14

SFTY

Safety speed enabled

status

0: Safety status disabled

1: Safety status enabled

Enable/disable the safety speed of the controller using the “safety speed command bit” of

device control register 1.

13

PWR

Controller ready status 0: Controller busy

1: Controller ready

This bit indicates whether or not the controller can be controlled externally. Normally this bit

does not become 0 (busy).

12

SV

Servo ON status

0: Servo OFF

1: Servo ON

The servo ON status is indicated. After a servo ON command is issued, this bit will remain 0

until the servo ON delay time set by a parameter elapses.

If the servo cannot be turned ON for some reason even after a servo ON command is

received, this bit will remain 0.

The RC controller does not accept any movement command while this bit is 0.

11

PSFL

Missed work part in

push-motion operation

0: Normal

1: Missed work part in push-motion operation

This bit turns 1 when the actuator has moved to the end of the push band without contacting

the work part (= the actuator has missed the work part) according to a push-motion operation

command.

Operation commands other than push-motion do not change this bit.

10

ALMH

Major failure status

0: Normal

1: Major failure alarm present

This bit will turn 1 if any alarm at the cold start level or operation cancellation level is

generated.

Alarms at the operation cancellation level can be reset by using an alarm reset command, but

resetting alarms at the cold start level requires turning the power supply off and then on

again.

9

ALML

Minor failure status

0: Normal

1: Minor failure alarm present

This bit will turn 1 when a message level alarm is generated.

8

ABER

Absolute error status

0: Normal

1: Absolute error present

This bit will turn 1 if an absolute error occurs in case the absolute specification is set.

7

BKRL

Brake forced-release

status

0: Brake actuated

1: Brake released

This bit indicates the status of brake operation. Normally the bit remains 1 while the servo is

ON. Even when the servo is OFF, changing the “brake forced-release command bit” in device

control register 1 to 1 will change this bit to 1.

6

-

Cannot be used

5

STP

Pause status

0: Normal

1: Pause command active

This bit remains 1 while a pause command is input.

If the PIO/Modbus Switch Setting (5.4.16 or 6.5.16) is PIO enabled, paused PIO signals are

monitored (set the switch to AUTO in case of RC controllers with a mode toggle switch). If

Modbus is enabled, the Pause Commands (5.4.6 or 6.5.6) are monitored.

4

HEND

Home return

completion status

0: Home return not yet complete

1: Home return complete

This bit will become 1 when home return is completed. In case the absolute specification is

set, the bit is set to 1 from the startup if absolute reset has been completed.

If a movement command is issued while this bit is 0, an alarm will generate.

3

PEND

Position complete

status

0: Positioning not yet complete

1: Position complete

This bit turns 1 when the actuator has moved close enough the target position and entered

the positioning band. It also turns 1 when the servo turns on after the actuator has started,

because the controller recognizes that the actuator has completed a positioning to the current

position.

This bit will also become 1 during the push-motion operation as well as at the completion.

2

CEND Load cell calibration

complete

0: Calibration not yet complete

1: Calibration complete

This bit turns 1 when the load cell calibration command (CLBR) has been successfully

executed.

1

CLBS Load cell calibration

status

0: Calibration not yet complete

1: Calibration complete

Regardless of whether or not a load cell calibration command has been issued, this bit is 1 as

long as a calibration has completed in the past.

0

-

Cannot be used