Modbus – IAI America ROBO Cylinder Series User Manual

Page 228

Advertising
background image

6. Modbus

ASCII

220

Modbus

(4) Sample query

A sample query that reads the system status (address 9008

H

) in a controller of axis No. 0 is shown

below.

Query: 01 03 90 08 00 02 62 [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Start address [H]

‘9’, ‘0’, ‘0’, ‘8’

39303038

Number of registers [H]

‘0’, ‘0’, ‘0’, ‘2’

30303032

Error check [H]

‘6’, ‘2’ (In accordance with LRC calculation) 3632

End

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 01 03 04 00 0C 00 11 DB [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H]

‘0’, ‘4’ (4 bytes = 2 registers)

3034

Data 1 [H]

‘0’, ‘0’, ‘0’, ‘C’

30303043

Data 2 [H]

‘0’, ‘0’, ‘1’, ‘1’

30303131

Error check [H]

‘D’, ‘B’ (In accordance with LRC calculation) 4442

End

‘CR’, ‘LF’

0D0A

Note The data of the response example is simply an example and will vary depending on

various conditions.