6. Modbus

ASCII

228

Modbus

(4) Sample query

A sample query that reads the startup time (address 9010

H

) of a controller of axis No. 0 is shown

below.

Query: 01 03 90 10 00 02 5A [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Start address [H]

‘9’, ‘0’, ‘1’, ‘0’

39303130

Number of registers [H]

‘0’, ‘0’, ‘0’, ‘2’

30303032

Error check [H]

‘5’, ‘A’ (In accordance with LRC calculation) 3541

End

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 01 03 04 02 38 C0 94 6A [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H]

‘0’, ‘4’ (4 bytes = 2 registers)

3034

Data 1 [H]

‘0’, ‘2’, ‘3’, ‘8’

30323338

Data 2 [H]

‘C’, ‘0’, ‘9’, ‘4’

43303934

Error check [H]

‘6’, ‘A’ (In accordance with LRC calculation) 3641

End

‘CR’, ‘LF’

0D0A

The system timer value is “0238C094” o Convert into decimal number o 37273748 ms

The total time since the controller power is turned on is 10.3538 hours.

Note The data of the response example is simply an example and will vary depending on

various conditions.