6. Modbus

ASCII

267

Modbus

*1 If the CLBR is turned OFF during this period, calibration will not be performed because the

signal is not yet recognized as having been input.

*2 If the CLBR is turned OFF during this period, an alarm will generate.

(4) Response

A response message to be sent following a successful change should be the same as the query.

If any invalid data has been sent, an exception response (refer to 7) will be returned or no response

will be returned at all.

(5) Example of use

Calibrate the dedicated load cell connected to controller axis 0.

Query 01 05 04 26 FF 00 D1

Field

ASCII mode 8-bit data

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘5’

3035

Start address [H]

‘0’, ‘4’, ‘2’, ‘6’

30343236

Changed data [H]

‘F, , ‘F’; ‘0’, ‘0’

46463030

Error check [H]

‘D’, ‘1’ (In accordance with LRC calculation)

4431

End

‘CR’, ‘LF’

0D0A

If the change is successful, the response message will be the same as the query.

Input is recognized after

the signal remains ON for

20 ms

*1

.

Calibration time

*2

CLBR

Turn OFF the CLBR after confirming

that the CEND has turned ON.

When the calibration was successful, the CEND turns ON.

While the CLBR is OFF, the CEND remains OFF.