Input Configuration for
Pulse Testing

Set up these signals by using the Outputs tab of the digital inputs
Signal Connections dialogbox in RSLogix Guard PLUS! software.

Name

Description

Type

Initial
Value

Notes

Number of Pulse Channels

Number of pulse outputs being used

USINT

1 to 8

1…4 for 1753-IB16
1…8 for GuardPLC 1600/2000 controllers
1…8 for 1753-IB20XOB8
1…2 for 1753-IB8XOB8 and 1753-IB16XOB8

Pulse Slot

Slot occupied by the module with the
pulsed outputs

UDINT —

2 for GuardPLC 1600 controllers
2 for 1753-IB20XOB8
1 for 1753-IB16
3 for 1753-IB8XOB8
3 for 1753-IB16XOB8
1…6 for GuardPLC 2000 controllers
(wherever 1755-IB24XOB16 is located)

Pulse Delay

Pulse delay is both the low pulse
width and pulse test duration.

UINT

400
(default)

Values in

μ

s from 5…2000.

Error Code

Error code for each switch

BYTE

N/A

See

Appendix B

for error code descriptions.

Value

Value for each switch

BOOL

DI[xx].PulseChannel

Indicates which pulse output is
sourcing the input channel

USINT

1 to 8

1…4 for 1753-IB16
1…8 for GuardPLC 1600/2000 controllers
1…8 for 1753-IB20XOB8
1…2 for 1753-IB8XOB8 and 1753-IB16XOB8

DO[xx].Value

Initialization value for the pulse
outputs

BOOL

TRUE

Each pulse output must be activated.