Appendix B System Signal Variables

High-Speed Counter Variables For GuardPLC 1200 and 2000
Controllers

The GuardPLC 1200 and GuardPLC 2000 controllers support these
variables for counter I/O parameters.

AO[0x].Value

(1)

Write

Output value of analog output channels
Voltage mode: -10V…10V = -1000…1000
Current mode: 0 mA…20 mA = 0…1000

for values between -1000… 0, the output current is 0 mA

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

0xFB04

analog output module for GuardPLC 2000 controller

0xFFFF

missing module in GuardPLC 2000 chassis

Board.State

Read

Error mask for the module

0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in

(1) 0x = output channels 01…08.

I/O Data

Read/Write

Description

I/O Data

Read/Write

Description

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

0x0003

counter module for GuardPLC 1200 controller

0xFC03

counter module for GuardPLC 2000 controller

0xFFFF

missing module in GuardPLC 2000 chassis