Wire the 1753-OW8 Relay Output Module

Introduction

Safety-related Relay
Outputs

The module has 8 isolated relay outputs whose status is indicated via
status indicators.

An output is in a safety state when it is de-energized. When a fault
occurs, all outputs are switched off. Errors in one or more channels
are indicated by the FAULT status indicator. In addition, the system
status can be evaluated in the user program.

If the 1753-OW8 module faults, all 8 outputs are switched off. This is
indicated by the FAULT status indicator.

Each output has 2 safety relays with positively guided contacts and
one MSR type relay. Internal, non-replaceable fuses are used to limit
the switching current of the output contacts to 60% (3.15 A) of the
maximum admissible AC switching current. For DC switching, the
relay contact circuits must be additionally equipped with an external
fuse rated no higher than the maximum admissible DC switching
capacity.

Terminal Connections

See the wire size and terminal torques specifications on page

294

.

Relay outputs are connected to these terminals.

Topic

Page

Safety-related Relay Outputs

99

Terminal Connections

99

Voltage Supply Considerations

100

Terminal Number

Designation

Relay Output

1

DO1

Contact 1, terminal A

2

Contact 1, terminal B

3

DO2

Contact 2, terminal A

4

Contact 2, terminal B

5

DO3

Contact 3, terminal A

6

Contact 3, terminal B