Check hh status – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 193

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

193

Configure Peer-to-Peer Communication Chapter 17

4. For all controllers in your project, re-adjust the Watchdog Times

to their individual optimum values.

5. Start the project and let it run for a while.

6. If you encounter controller errors due to a Watchdog Time that

is too short, increase the Watchdog Time. Otherwise, continue
with the network optimization.

Check HH Status

In the Control Panel, click the HH Status tab.

The HH Status displays the following information.

Read the RspT min parameter. This is the minimum time needed for
the communication modules (COM) of two controllers to talk to each
other. Refresh RspT values with Communication>Update HH State, if
Token Passing is OFF.

TIP

After these modifications, you must re-compile the
project with the Code Generator and download the
routines in the controllers again.

Parameter

Explanation

Bus Cycle Time Time in milliseconds for a Token cycle. The value is 0, if Token Passing is

off (any Cleanroom profile).

Resource

Name of the controller

LinkId

Controller network ID

State

Status of the communication

RspT

If Link Mode is TCS direct (Token Passing OFF), RspT is the

ResponseTime of the HH profile for a message from PES

1

PES

2

PES

1

, based on the network hardware and topology. This parameter

cannot be changed by the user.

If Link Mode is TCS TOKCYC (Token Passing ON), RspT is part of the Bus

Cycle Time.

Link Mode

TCS direct when Token Passing is OFF.

TCS TOKCYC when Token Passing is ON.

Token Group ID ID of the Token Group