Analog input signals for 1753-if8xof4 modules – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 323

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

323

System Signal Variables Appendix B

Analog Input Signals for 1753-IF8XOF4 Modules

The 1753-IF8XOF4 module supports these analog input signals.

I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type: 0x001E

Module.Error.Code

Read

Error mask for the module

0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040/80

No I/O processing because configured module is not plugged in

AI.Error Code

Read

Error mask for all analog inputs

0x0001

Module error

0x0004

MEZ test, time monitoring of conversion

0x0008

FTZ test: walking bit of data bus faulty

0x0010

FTZ test: Operating voltages faulty

0x0020

MEZ test, active disconnection failed

0x0040

A/D conversion faulty

0x0080

MEZ test: cross links of MUX faulty

0x0100

MEZ test: walking bit of data bus faulty

0x0200

MEZ test: multiplexer addresses faulty

0x0400

MEZ test: operating voltages faulty

0x0800

MEZ test: measuring system (characteristic) faulty (unipolar)

0x1000

MEZ test: measuring system (final values, zero point) faulty
(unipolar)

0x8000

A/D conversion faulty (DRDY_HIGH)