Use the Control Panel to Monitor Status Chapter 14

EIP Protocol Tab

This Field

Displays

Peer IP

IP address of communication partner

Peer Status

Status of Peers, either Run or Idle.

If peer does not provide run idle information, nothing can be displayed!

Connection Type

Displays the Connection Type, Originator or Target, that the controller acts as in this connection.

Connection State

The status of connection.

1 = Connecting Configuring – In the process of opening a new connection.

2 = Spare

3 = ConnectionEstablished – Connection is active.

4 = ConnectionTimedOut – Connection has timed out; will stay in this state at least for some time if
WatchdogTimeoutAction is set to TimeoutManualReset or TimeoutDelayAutoReset.

5 = ConnectionDeferredDelete – Connection is about to be deleted and waiting for child connections to be
closed first.

6 = ConnectionClosing – In the process of closing the connection.

Input

Associated input assembly Id with the connection or 0 if none. For scanner connections of the controller these field
shows the assembly id data is read from.

Output

Associated output assembly id with the connection or 0 if none. For scanner connections of the controller these
field shows the assembly id data is written to.

Sent

Number of sent packets on this connection.
Counter wraps with 2

32

packets.

Received

Number of received packets on this connection.
Counter wraps with 232 packets.

Bad Messages

Number of received or dropped messages for that connection. You can reset this value by pressing Counter Reset.

PRPI

Produced Requested Packet Interval (µs).

CRPI

Consumed Requested Packet Interval (µs).

MinPITime

Minimum Packet Interval Time (µs).

MaxPITime

Maximum Packet Interval Time (µs).

LastPITime

Last Packet Interval Time (µs).

AvrPITime

Average Packet Interval Time (µs).