Page 219

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

219

Use GuardPLC Controller as an Adapter Chapter 19

Open a Class 1 Connection
from a Logix Controller to
the GuardPLC Controller

The following example demonstrates making a connection to a Logix
controller, specifically a ControlLogix controller, with a 1756-ENBT or
1756-ENET module to a GuardPLC controller. You can also open
connections to CompactLogix controllers. In a Class 1 connection,
data is cyclically exchanged based on a time interval (RPI).

Configure the Logix Controller in RSLogix 5000 Software

1. In RSLogix 5000 software, create a new project for the Logix

controller.

2. Add the Ethernet adapter module to the I/O Configuration

a. Right-click I/O Configuration and choose New Module.

b. In the Select Module Type dialog box, click the 1756-ENBT or

1756-ENET module type.

c. Click OK.

d. In the Module Properties dialog box, type the IP address and

the slot number of the 1756-ENBT module.

e. Click Finish.

RSLogix 5000 software displays the new 1756-ENBT module
under the I/O Configuration.

3. Right-click the new 1756-ENBT icon and choose New Module.