Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 248

Advertising
background image

248

Publication 1753-UM001C-EN-P - March 2010

Chapter 19 Use GuardPLC Controller as an Adapter

3. Double-click the object to open the Properties dialog box.

4. Enter the desired Field Width and Decimal Point display

information.

5. Enter a name for the Read Tag.

6. Click the Edit Tag button to open the Tag Form dialog box.

7. Configure the tag as shown below.

Parameter

Setting

Messaging Type

CIP

Node Name

Enter the name of the GuardPLC controller that will receive the command.

Service Code

Choose Get Attribute Single to indicate that this is a read operation.

Class Code

Enter 4, for an assembly object.

Instance Number

Enter 121 to indicate the GuardPLC target input assembly that was created for the
PanelView Standard terminal to read from.

Attribute

Enter 3 to provide access to the assembly object instance data.

Byte Offset

Index into the GuardPLC output assembly x number of bytes, then read the data.