Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 248
248
Publication 1753-UM001C-EN-P - March 2010
Chapter 19 Use GuardPLC Controller as an Adapter
3. Double-click the object to open the Properties dialog box.
4. Enter the desired Field Width and Decimal Point display
information.
5. Enter a name for the Read Tag.
6. Click the Edit Tag button to open the Tag Form dialog box.
7. Configure the tag as shown below.
Parameter
Setting
Messaging Type
CIP
Node Name
Enter the name of the GuardPLC controller that will receive the command.
Service Code
Choose Get Attribute Single to indicate that this is a read operation.
Class Code
Enter 4, for an assembly object.
Instance Number
Enter 121 to indicate the GuardPLC target input assembly that was created for the
PanelView Standard terminal to read from.
Attribute
Enter 3 to provide access to the assembly object instance data.
Byte Offset
Index into the GuardPLC output assembly x number of bytes, then read the data.