Appendix B System Signal Variables

DO.State

(1)

Read

Error mask for all digital outputs

0x0000

No errors detected

0x0001

Error of the DO section of the module

0x0002

Within the multiple error occurrence time: safety switch 1 faulty

0x0004

Within the multiple error occurrence time: safety switch 2 faulty

0x0008

Within the multiple error occurrence time: test sample tests faulty

0x0010

Within the multiple error occurrence time: readback channels faulty

0x0020

Within the multiple error occurrence time: active switch-off faulty

0x0100

Within the safety time: CS signals faulty

0x0200

All outputs switched off; total current too high

0x0400

Within the safety time: temperature limit 1 exceeded

0x0800

Within the safety: temperature limit 2 exceeded

0x01000

Within the safety time: auxiliary voltage monitoring: undervoltage

0x02000

Within the multiple error occurrence time: status of the
safety switches

DO[0x].State

(1)(2)

Read

Error mask for digital output channels

0x00

No error detected; outputs driven as expected

0x01

Error in digital output module; outputs not driven

0x02

Output switched off due to overcurrent; outputs not driven

0x04

Error during readback of the digital output; outputs not driven

DO[0x].Value

(1)

Write

Output value of digital output channels

0

Output de-energized

1

Output activated

DI.State

Write

Error mask for all digital inputs

0x0000

No error detected

0x0001

Error of the DI section of the module

0x0002

Within the safety time: test sample test faulty

DI[xy].State

(3)

Read

Error mask of digital input channels

0x00

No error detected

0x01

Error in the digital input module; input value set to 0

DI[xy].Value

(2)

Read

Input values of digital input channels

0

Input not activated

1

Input activated

(1) Values are ORed.
(2) 0x = output channel 01…16 for GuardPLC 2000 controller and 01…08 for GuardPLC 1200, 1600, and 1800 controllers.
(3) xy = input channel 01…24 for GuardPLC 2000 and GuardPLC 1800 controllers and 01… 20 for GuardPLC 1200 and 1600 controllers.

I/O Data

Read/Write

Description