Chapter 4 Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Safety-related Digital Output Terminals

Digital outputs are connected to these terminals.

Safety-related Analog Input Terminals

The GuardPLC 1800 controller features 8 single-ended analog inputs.
Differential analog inputs cannot be used on the GuardPLC 1800
controller. Two- or four-wire transmitters can be used. These devices
can be powered from the transmitter supply terminal of the GuardPLC
1800 controller or from an external power supply. See

Appendix C

for

example wiring diagrams.

Terminal
Number

Designation

Function

Current

1

L-

Reference pole

2

1

Digital output 1

0.5 A

3

2

Digital output 2

0.5 A

4

3

Digital output 3

0.5 A

5

4

Digital output 4 (for increased load)

2.0 A

6

5

Digital output 5

0.5 A

7

6

Digital output 6

0.5 A

8

7

Digital output 7

0.5 A

9

8

Digital output 8 (for increased load)

2.0 A

10

L-

Reference pole

IMPORTANT

Unused analog inputs must be short-circuited. See page

51

.

1

2

3

4

5

6

1

2

3

4

1

L-

L-

DO

2

(2 A)

(2 A)

3

4

5

6

7

8

5

6

7

8

9

10

10

7

8

9

AI

T1 I1 L- T2 I2 L-

AI

T3 I3 L- T4 I4 L-

AI

T5 I4 L- T6 I6 L-

AI

T7 I7 L- T8 I8 L-

47 48 49 50 51 52

41 42 43 44 45 46

53 54 55 56 57 58

59 60 61 62 63 64

Advertising