Chapter 17 Configure Peer-to-Peer Communication

Choose a Peer-to-peer Profile

1. Click in the Profile column and choose one of the profiles.

Make sure that the profile is suitable for your network topology
and matches the HH profile.

See page

161

for a detailed description of all the profiles.

2. Click outside the table or press the Return key to activate the

selection.

The profile of the return path is automatically updated with the
new profile.

Define Peer-to-peer Parameters

The most important timing parameter of a safety related installation is
the Safety Time. Safety Time is the time a process can run with
incorrect controller outputs without affecting the safety of the process.

See the GuardPLC Controller Systems Safety Reference Manual,
publication

1753-RM002

for more details on the Safety Time.

The Worst Case Reaction Time (T

R

) is the time within which two

linked controllers must detect the occurrence of a physical input
signal at PES

1

and put out the resulting physical output signal at PES

2

.

To guarantee the integrity of the application, the requirement below
must always be fulfilled.

T

R

< Safety Time

When you choose a peer-to-peer profile, most parameters are
automatically preset. Because ReceiveTMO (safety-relevant) is part of
the Worst Case ReactionTime T

R

(see

Peer-to-peer Protocol Parameters