Appendix B System Signal Variables
Force Time
milliseconds
Read
Remaining running time during forcing; 0 if Force is inactive.
[DINT]
NON-SAFE
Power Supply
0-255
Read
GuardPLC 1200 and GuardPLC 2000
Controllers
0 = normal
1 = error of input power supply 24 VDC
2 = error of battery
4 = module error of power supply 5 V
8 = module error of power supply 3.3 V
16 = 5 V undervoltage
32 = 5 V overvoltage
64 = 3.3 V undervoltage
128 = 3.3 V overvoltage
255 = status does not exist
[BYTE]
NON-SAFE
GuardPLC 1600 and GuardPLC 1800
Controllers
0 = normal
1 = 24 VDC undervoltage
4 = 5 V undervoltage
8 = 3.3 V undervoltage
16 = 3.3 V overvoltage
[BYTE]
NON-SAFE
System Tick High
System Tick Low
milliseconds
Read
Ring counter with 64 bits, incremented in millisecond steps. [UDINT]
SAFE
Temperature State
0, 1, 2, 3,
255
Read
0 = normal
1 = high
2 = faulty
3 = very high
255 = status does not exist
[BYTE]
NON-SAFE (but for additional switch-off)
(1) Binary values are ORed.
System Variable
Unit/Value
Read/Write
Description
(1)
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems