Chapter 3 General Wiring Considerations

Shield-contact Plate
Connections

Shielded cabling is fed in from below so that the shielding can be
connected to the shield-contact plate by using a clip. Remove about 2
cm (0.79 in.) of the outer cable insulation so that the mesh is exposed
at the point where the cable is clipped to the plate. Position the clip
over the uninsulated cable shielding and push it into the slots of the
shield contact plate until it fits firmly in place, as shown below.

Detailed Wiring
Information

For detailed wiring information by product, see the table below.

To be sure that GuardPLC controllers and I/O modules are used in a
safety-related manner (SIL3 in accordance to IEC 61508), the whole
system, including connected sensors and encoders, must satisfy the
safety requirements described in the GuardPLC Controllers Safety
Reference Manual, publication

1753-RM002

.

IMPORTANT

Make sure that the mesh comes in direct contact with the
shield-contact plate. If the mesh does not touch the plate, the
cable is not grounded.

63 64

65

66 67 68

71 72

69 70

net

T

4

Cable Clip

Mesh

Shield-contact Plate

For

See

GuardPLC 1600, GuardPLC 1800 and
GuardPLC 1200 Controllers

Chapter 4

GuardPLC 2000 Controller

Chapter 5

1753-IB16, 1753-OB16, 1753-IB20XOB8
Modules

Chapter 6

1753-IB8XOB8

Chapter 7

1753-IB16XOB8

Chapter 8

1753-IF8XOF4

Chapter 9

1753-OW8

Chapter 10

Wiring Examples

Appendix C