Use unconnected cip messaging from a panelview, Standard terminal – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 243

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

243

Use GuardPLC Controller as an Adapter Chapter 19

9. Enter the IP address of the GuardPLC controller.

Use Unconnected CIP
Messaging from a
PanelView Standard
Terminal

Use the Generic CIP message profile to configure the PanelView
Standard terminal to exchange data with the GuardPLC controller.
Both devices must be connected to the EtherNet/IP network. You will
need PanelBuilder32 software, version 3.82.

xx or later, to configure

the PanelView Standard terminal.

Follow these steps to enable the PanelView Standard terminal to
message to the GuardPLC controller, acting as an adapter (target).

1. Create a GuardPLC Assembly Instance (input or output),

including the data type, assembly size, and assembly name. See
pages

215

and

216

.

2. Create a new EtherNet/IP application in PanelBuilder32

software.

3. Configure the PanelView terminal for EtherNet/IP

communication.

4. To perform read and write operations to the GuardPLC

controller’s target assemblies, add objects to the PanelView
Standard terminal’s application. Configure those objects for read
or write operation, using tags.

PLC-5 Controller

SLC 5/05 Controller

TIP

Make sure the Run/Idle header box is unchecked as
unconnected CIP messages do not use a Run/Idle
header.

Advertising