221

Use GuardPLC Controller as an Adapter Chapter 19

Exclusive Owner

To establish an exclusive owner connection, follow these steps.

1. Choose Data — SINT in the Comm Format Field.

2. Type the GuardPLC controller’s Input Assembly instance number

in the Input Assembly Instance field.

3. Type the size of the Input Assembly in the Input Size field.

4. Type the GuardPLC controller’s Output Assembly instance

number in the Output Assembly Instance field.

5. Type the size of the Output Assembly minus 4 bytes in the

Output Size field.

The data size in RSLogix 5000 software does not include the
4 bytes of the Run/Idle header, but these 4 bytes must be part of
the GuardPLC controller’s output assembly, because the
ControlLogix controller sends the 4-byte Run/Idle header to the
GuardPLC controller.

For example, if you created an output assembly of 6 bytes (6
BYTE signals assigned in RSLogix Guard PLUS! software), you
must enter an Output Size of 2 in RSLogix 5000 software,
because only the last 2 bytes contain the actual data.

IMPORTANT

This entry must exactly match the size of the input
assembly, or the GuardPLC adapter controller will return
an error.

The size of the input assembly is determined during the
signal connection process.