Open a connection to a logix controller, Create a producing data tag – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 260

260
Publication 1753-UM001C-EN-P - March 2010
Chapter 20 Use the GuardPLC Controller as a Scanner
Open a Connection to a
Logix Controller
The GuardPLC controller can establish a connection to a ControlLogix
or CompactLogix controller and read the data over this connection.
The data must be stored in the producing data tag in the Logix
controller. The data exchange is one-sided, from the Logix controller
to the GuardPLC controller. For exchanging data in both directions,
see
Open a Class 1 Connection from a Logix Controller to the
on page
Create a Producing Data Tag
1. Open your RSLogix 5000 project.
2. Click the Edit Tags tab.
3. Right-click an empty line and choose Edit Tag Properties.
4. Enter the tag name.
5. Set the tag type as Produced.
The Number of Consumers parameter dictates how many
scanners should be able to read from this tag at the same time.
6. Enter the Data Type.
7. Click OK to save the changes.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems