Analog output signals for 1753-if8xof4 modules – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 325

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

325

System Signal Variables Appendix B

Analog Output Signals for 1753-IF8XOF4 Modules

The 1753-IF8XOF4 module supports these analog output signals.

I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type: 0x

Module.Error.Code0069

Read

Error mask for the module

0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040/80

No I/O processing because configured module is not plugged in

AO.Error Code

Read

Error mask for all analog inputs

0x0001

Module error

0x0002

MEZ test: safety switch 1 failed

0x0004

MEZ test: safety switch 2 failed

0x0008

FTZ test: of test pattern failed

0x0010

FTZ test: error checking coefficients

0x0400

FTZ test: 1. Temperature threshold exceeded.

0x0800

FTZ test: 2. Temperature threshold exceeded.

0x2000

MEZ test: status of safety switches

0x4000

MEZ test: active disconnection by watchdog failed

AO[xx].Error Code

(1)

Read

Error code of analog input channels

0x01

Error in the analog output unit

0x80

AO[xx].Value not in the specified range.

AO[xx].Value

Write

Output value of AO channels:
Current characteristic: 0…2000 (0 mA…20 mA)
Current characteristic: -2000…0 (0 mA)

Values are tested for plausibility before standardization.
Current characteristic:

Values < 0: standardization with 0

Values < sampling point LOW: standardization with sampling point LOW

Values > sampling point HIGH: standardization with sampling point HIGH

IMPORTANT: Outputs must not be used as safety-related outputs!

AO[xx].Used

Write

Configures the channel for operation

0

Channel is not in operation.

1

Channel is operating.

(1) xx = affected output channel of the controller or module.